14 CFR · Part 27

14 CFR § 27.967

Fuel tank installation.

← Previous SectionNext Section →
Read in Subpart E
Part 27 Contents
  • Subpart A: General
  • Subpart B: Flight
  • Subpart C: Strength Requirements
  • Subpart D: Design and Construction
  • Subpart E: Powerplant
  • Subpart F: Equipment
  • Subpart G: Operating Limitations and Information
  • Appendix A to Part 27: Instructions for Continued Airworthiness
  • Appendix B to Part 27: Airworthiness Criteria for Helicopter Instrument Flight
  • Appendix C to Part 27: Criteria for Category A
  • Appendix D to Part 27: HIRF Environments and Equipment HIRF Test Levels
(a)

Each fuel tank must be supported so that tank loads are not concentrated on unsupported tank surfaces. In addition—

(1)

There must be pads, if necessary, to prevent chafing between each tank and its supports;

(2)

The padding must be nonabsorbent or treated to prevent the absorption of fuel;

(3)

If flexible tank liners are used, they must be supported so that it is not necessary for them to withstand fluid loads; and

(4)

Each interior surface of tank compartments must be smooth and free of projections that could cause wear of the liner unless—

(i)

There are means for protection of the liner at those points; or

(ii)

The construction of the liner itself provides such protection.

(b)

Any spaces adjacent to tank surfaces must be adequately ventilated to avoid accumulation of fuel or fumes in those spaces due to minor leakage. If the tank is in a sealed compartment, ventilation may be limited to drain holes that prevent clogging and excessive pressure resulting from altitude changes. If flexible tank liners are installed, the venting arrangement for the spaces between the liner and its container must maintain the proper relationship to tank vent pressures for any expected flight condition.

(c)

The location of each tank must meet the requirements of § 27.1185 (a) and (c).

(d)

No rotorcraft skin immediately adjacent to a major air outlet from the engine compartment may act as the wall of the integral tank.

Regulations Referenced

14 CFR 27.1185

Reflects the eCFR edition current as of September 29, 2026. Retrieved from ecfr.gov on October 16, 2026.